Iai-america PCON-CF Bedienungsanleitung Seite 182

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 226
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 181
164
10. Troubleshooting
Code Message name Description
30C No connected axis This message indicates that no controller address is recognized.
Cause: [1] The controller is not operating properly.
[2] Only the supplied communication cable (SGA/SGB) is
disconnected.
[3] If a SIO converter is used, 24V is supplied to the
converter but the link cable is not connected.
[4] The ADRS switch settings are duplicated by mistake
when multiple controllers are linked.
Action: [1] Check if the RDY lamp on the controller is lit. If the lamp
is not lit, the controller is faulty.
[2] If a spare teaching pendant is available, replace the
current pendant with the spare unit, or with a PC, and see
if the message disappears.
[3] Supply power after connecting the link cable between the
converter and controller.
[4] Make sure the ADRS switch settings are not duplicated.
If the message is still displayed after taking the above actions, please
contact IAI.
Seitenansicht 181
1 2 ... 177 178 179 180 181 182 183 184 185 186 187 ... 225 226

Kommentare zu diesen Handbüchern

Keine Kommentare